A duct fitting loss coefficient relates a fitting’s total-pressure loss to the velocity pressure at a defined reference section. This manufacturer comparison shows four 8-inch 90° elbow constructions. The coefficient varies with geometry, and the source’s values should not be transferred to a different diameter, radius, vane arrangement, or measurement basis without checking the relevant fitting data.
Air Duct Fitting Loss Coefficients table
Air duct elbow loss coefficients for selected construction
McGill AirFlow comparison for four 8-inch 90° elbow constructions, using its stated fitting and velocity-pressure basis.
1–4 of 4 matching rows (4 total)
Free engineering resource
Unlock CSV downloads and printing
Enter your email to download the displayed table page as CSV or print it.
CSV and print access for this browser session
Submit the form to unlock CSV downloads and printing.
Search and sort apply to all 4 rows. Print and CSV include only the 4 rows shown on this page.
Definition of coefficient
McGill AirFlow defines fitting loss coefficient C as the change in total pressure divided by velocity pressure. Rearranging gives ΔTP = C × VP. If velocity pressure is held constant, doubling C doubles the estimated total-pressure loss. The coefficient is dimensionless, but it is meaningful only with the reference section and fitting configuration used to establish it.
What the comparison covers
All four rows are for 90° elbows with an 8-inch diameter. The source compares a die-stamped or pressed elbow with a 1.5 centerline radius, a five-piece elbow with the same stated radius, and two mitered designs with and without turning vanes. The values provide a controlled comparison across construction types rather than a broad catalog for every fitting.
Geometry changes the loss
The smooth die-stamped elbow has the lowest listed coefficient in the comparison. A multi-piece elbow is higher, and the mitered configurations increase further, with turning vanes reducing the value relative to the mitered elbow without vanes. The trend is tied to the exact tested forms; vane profile, count, spacing, and placement can change the result.
Use pressure loss carefully
The source example calculates velocity from flow and area, determines velocity pressure, then multiplies by C. For a constant-area elbow, the guide explains that the change in static pressure equals the change in total pressure. A transition or branch can change velocity, so static and total pressure changes are not interchangeable.
Do not scale coefficients blindly
A coefficient measured for one size and geometry may not remain the same for a different diameter, radius ratio, aspect ratio, or construction. Flow regime, density, surface roughness, and installation effects can also matter. Use a fitting database or manufacturer data that matches the actual geometry and reference area when calculating a real duct network.
System effects and close spacing
Fittings installed close together can interact because the velocity profile has not recovered between them. An elbow followed immediately by a branch or transition may not have the same loss as an isolated fitting. The individual coefficient comparison does not model an entire duct system, fan curve, leakage, or balancing damper.
Worked interpretation
If the selected duct section has velocity pressure VP, multiply it by the matching coefficient to estimate the guide’s total-pressure loss. Keep units consistent for VP and pressure loss. The coefficient alone is not pressure, airflow, or fan power. A pressure-loss estimate needs flow, air density, cross-section, and the correct fitting record.
Design and verification
Use the table for preliminary comparison, then verify the actual fitting dimensions, fabrication method, vane details, and manufacturer performance data. Add losses from straight duct, filters, coils, dampers, and other components. Check the full system curve against the fan selection and operating point. A qualified HVAC designer should review consequential airflow or pressure requirements.
Applying the reference
Before using a row, confirm its units, assumptions, source edition, and fit with the actual project. These values support preliminary learning and comparison; they do not replace an approved drawing, current product data, or qualified review of the geometry, material, and operating conditions. Keep the selected inputs and method with the design record so another engineer can reproduce the result and identify when a different model applies. Recheck the source when specifications or product documentation change.
Source
McGill AirFlow, Duct System Design Guide. The table identifies sourced and calculated values. Accessed October 18, 2026.