Equivalent length converts a fitting’s estimated flow resistance into an equivalent length of straight pipe of the same size. The ASHRAE table below lists five common fittings and valves for nominal pipe diameters from 15 to 350 mm. It comes from the steam-piping section of the 2025 ASHRAE Handbook—Fundamentals, so its values retain that context and should not be treated as universal loss data for every fluid or fitting design.
Equivalent pipe lengths for fittings
ASHRAE equivalent lengths of steam-pipe fittings
Equivalent straight-pipe lengths from ASHRAE Handbook—Fundamentals 2025 SI Chapter 22 Table 31.
1–50 of 75 matching rows (75 total)
Free engineering resource
Unlock CSV downloads and printing
Enter your email to download the displayed table page as CSV or print it.
CSV and print access for this browser session
Submit the form to unlock CSV downloads and printing.
| Nominal pipe diameter (mm) (mm) ↕ | Fitting or valve ↕ | Equivalent straight length (m) (m) ↕ | Source condition ↕ |
|---|---|---|---|
| 15 | Standard elbow | 0.4 | ASHRAE Table 31; steam-piping sizing context. |
| 15 | Side-outlet tee | 0.9 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 15 | Gate valve (fully open) | 0.1 | ASHRAE footnote: valve in full-open position. |
| 15 | Globe valve (fully open) | 4 | ASHRAE footnote: valve in full-open position. |
| 15 | Angle valve (fully open) | 2 | ASHRAE footnote: valve in full-open position. |
| 20 | Standard elbow | 0.5 | ASHRAE Table 31; steam-piping sizing context. |
| 20 | Side-outlet tee | 1.2 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 20 | Gate valve (fully open) | 0.1 | ASHRAE footnote: valve in full-open position. |
| 20 | Globe valve (fully open) | 5 | ASHRAE footnote: valve in full-open position. |
| 20 | Angle valve (fully open) | 3 | ASHRAE footnote: valve in full-open position. |
| 25 | Standard elbow | 0.7 | ASHRAE Table 31; steam-piping sizing context. |
| 25 | Side-outlet tee | 1.5 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 25 | Gate valve (fully open) | 0.1 | ASHRAE footnote: valve in full-open position. |
| 25 | Globe valve (fully open) | 7 | ASHRAE footnote: valve in full-open position. |
| 25 | Angle valve (fully open) | 4 | ASHRAE footnote: valve in full-open position. |
| 32 | Standard elbow | 0.9 | ASHRAE Table 31; steam-piping sizing context. |
| 32 | Side-outlet tee | 1.8 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 32 | Gate valve (fully open) | 0.2 | ASHRAE footnote: valve in full-open position. |
| 32 | Globe valve (fully open) | 9 | ASHRAE footnote: valve in full-open position. |
| 32 | Angle valve (fully open) | 5 | ASHRAE footnote: valve in full-open position. |
| 40 | Standard elbow | 1.1 | ASHRAE Table 31; steam-piping sizing context. |
| 40 | Side-outlet tee | 2.1 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 40 | Gate valve (fully open) | 0.2 | ASHRAE footnote: valve in full-open position. |
| 40 | Globe valve (fully open) | 10 | ASHRAE footnote: valve in full-open position. |
| 40 | Angle valve (fully open) | 6 | ASHRAE footnote: valve in full-open position. |
| 50 | Standard elbow | 1.3 | ASHRAE Table 31; steam-piping sizing context. |
| 50 | Side-outlet tee | 2.4 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 50 | Gate valve (fully open) | 0.3 | ASHRAE footnote: valve in full-open position. |
| 50 | Globe valve (fully open) | 14 | ASHRAE footnote: valve in full-open position. |
| 50 | Angle valve (fully open) | 7 | ASHRAE footnote: valve in full-open position. |
| 65 | Standard elbow | 1.5 | ASHRAE Table 31; steam-piping sizing context. |
| 65 | Side-outlet tee | 3.4 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 65 | Gate valve (fully open) | 0.3 | ASHRAE footnote: valve in full-open position. |
| 65 | Globe valve (fully open) | 16 | ASHRAE footnote: valve in full-open position. |
| 65 | Angle valve (fully open) | 8 | ASHRAE footnote: valve in full-open position. |
| 80 | Standard elbow | 1.9 | ASHRAE Table 31; steam-piping sizing context. |
| 80 | Side-outlet tee | 4 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 80 | Gate valve (fully open) | 0.4 | ASHRAE footnote: valve in full-open position. |
| 80 | Globe valve (fully open) | 20 | ASHRAE footnote: valve in full-open position. |
| 80 | Angle valve (fully open) | 10 | ASHRAE footnote: valve in full-open position. |
| 100 | Standard elbow | 2.7 | ASHRAE Table 31; steam-piping sizing context. |
| 100 | Side-outlet tee | 5.5 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 100 | Gate valve (fully open) | 0.6 | ASHRAE footnote: valve in full-open position. |
| 100 | Globe valve (fully open) | 28 | ASHRAE footnote: valve in full-open position. |
| 100 | Angle valve (fully open) | 14 | ASHRAE footnote: valve in full-open position. |
| 125 | Standard elbow | 3.3 | ASHRAE Table 31; steam-piping sizing context. |
| 125 | Side-outlet tee | 6.7 | ASHRAE footnote: applies to a tee diverting flow in the main to the last riser. |
| 125 | Gate valve (fully open) | 0.7 | ASHRAE footnote: valve in full-open position. |
| 125 | Globe valve (fully open) | 34 | ASHRAE footnote: valve in full-open position. |
| 125 | Angle valve (fully open) | 17 | ASHRAE footnote: valve in full-open position. |
Search and sort apply to all 75 rows. Print and CSV include only the 50 rows shown on this page.
How to use the table
Choose the nominal diameter that matches the pipe run and select the row for the actual flow path. Add the equivalent length for each fitting to the measured straight-pipe length. For example, ASHRAE’s worked example uses a 100 mm run with a 0.6 m gate-valve allowance, four standard elbows at 2.7 m each, two tees at 5.5 m each, and 40 m of measured pipe. The total equivalent run is 62.4 m.
That calculation is a simple sum, but the fitting selection is not arbitrary. The table labels the tee as a side-outlet tee and a footnote restricts its value to a tee diverting flow in the main to the last riser. The valve footnote says the valve is fully open. A throttled valve, a different tee flow path, or a fitting with a materially different geometry does not automatically have the listed equivalent length.
Keep the source scope attached
ASHRAE introduces the table while discussing steam-pipe pressure drop. It describes fitting and valve resistance as a length of straight run of the same size. The equivalent length of run used in pipe sizing is distinct from the actual measured pipe length. In an initial sizing pass, a designer may estimate this allowance; after selecting pipe sizes, the fitting lengths can be revisited using the actual sizes and routing.
Do not transplant the table into a chilled-water, compressed-air, chemical, or fire-protection calculation without checking whether the underlying method and fitting data are appropriate. Many systems use resistance coefficients K, manufacturer pressure-drop data, or code-specific equivalent-length tables. A valve’s internal design, opening position, and flow coefficient can change the loss substantially. The system’s fluid properties, velocity, Reynolds number, and roughness also affect pressure-drop calculations.
Worked check and common errors
For a 100 mm steam line with four standard elbows and one fully open gate valve, the table gives 4 × 2.7 m + 0.6 m = 11.4 m of fitting allowance. If the measured straight pipe is 40 m, the combined equivalent length for those items is 51.4 m. This subtotal intentionally excludes tees, strainers, reducers, and other components not specified in the example.
Do not add the table value to the pipe length more than once. Do not use an elbow allowance for a tee branch or a valve allowance for a partly closed control valve. Keep units aligned: add metres to metres, and select a row by nominal diameter rather than treating the diameter number as an equivalent length. Record the fittings that were included so another reviewer can reproduce the total.
Engineering limits
Equivalent length is a convenient approximation rather than a geometric property of a component. The result depends on the pipe-size basis and the loss model used to derive or apply it. For critical pressure-drop work, a manufacturer’s data or a validated K-factor method may be preferable. The table is not a pressure rating, valve sizing chart, or substitute for checking allowable velocity and system operating conditions.
ASHRAE notes that the exact fitting length can depend on pipe sizes that are not yet known during preliminary sizing. Once the run is laid out, recalculate using the actual components and dimensions. If the estimated allowance materially changes the available pressure drop or equipment choice, use better source data before releasing the design.
Source
Values and footnotes are transcribed from ASHRAE Handbook—Fundamentals 2025 SI, Chapter 22, Table 31. The associated text and worked example define the equivalent-length context. Verify the fitting type, pipe-size basis, fluid service, and method before using a value in a project calculation.
